Device warns of residual electrical
power
Device gives a clear, visual indication of any residual power within an electrical enclosure, leading to higher levels of safety for operating, service or maintenance personnel.
A Universal Power Alert (UPA) device gives a clear, visual indication of any residual power within an electrical enclosure, leading to higher levels of safety for operating, service or maintenance personnel The latest UPA-130 model, now available from Marsh Bellofram Europe, is a smaller unit, which has been designed to be fitted in a standard 30mm diameter panel knockout, while the original UPA-100 fitted a 1.1/4in size conduit knockout
This article was originally published on Manufacturingtalk on 14 Oct 2002 at 8.00am (UK)
Related stories
High pressure regulators reduce gas pressures
Direct acting high pressure regulators have been designed for reducing high inlet gas and compressed air pressures down to lower supply pressures suitable for precision regulation.
3D models of off-the-shelf telescopic slides
Telescopic ball bearing slide designer and manufacturer, Accuride International, has produced optimised 3D models of its 'off-the-shelf' products which can be downloaded via its website.
Both products enjoy the same operating principles and provide identical levels of safety when fitted to control panels, circuit breaker boxes or other types of enclosed electrical isolating devices.
The features include the verification of zero-energy for safe working conditions, or the detection and indication of either single or three phase AC voltages within an enclosed unit.
The presence of DC or stored energy is also similarly identified.
Further reading
Full digital set-up on tension control system
A new digital tension controller is claimed to be one of the most comprehensive tension control systems currently available
Differential drives offer intelligent phase shifts
Using the advantages offered by differentials companies operating in industries such as printing, packaging and labelling can expect to make significant gains.
This helps to reduce the potential for arc-flash and electrocution risk for personnel having the responsibility for undertaking maintenance or repairs on electrical machinery or equipment.
The UPA power alert is hard wired to the circuit breaker or other disconnect devices and pre-verifies from the outside of the control panel or enclosure that full electrical isolation exists.
The power alert incorporates redundant circuitry and is powered by the same voltage that it indicates, and so identifies hazardous conditions before access is gained to enclosures.
It also enhances compliance with NFPA and OSHA recommendations on 'the control of hazardous energy'.
The eight LED indicator/detector visually alerts to dangerous conditions where ac potential occurs between any combination of the four monitored input lines (L1, L2, L3 and earth or GND).
Two LED lights (designated + and - ) are assigned to each input line.
For each of these lines carrying an AC potential (bi-polar), both LEDs are illuminated and will flash.
In the event of dc or stored energy potential, the +ve or - ve respective LED will be illuminated for the appropriate + or - line.
Operational power range is 40 to 750V AC, 50/60/400Hz for single and three phase supplies.
DC or stored energy is 30 to 1000V DC.
In all cases line-to-line and line-to-GND leakage conditions are identified.
Power consumption is approximately 1.2W at 750V AC and the LED flash rate/s varies from approximately 1.5 to 9 with the rate increasing as the voltages get higher.
Supplied in NEMA 4X totally encapsulated housings for environmental protection, the UPA devices are supplied with 6ft (1.8m) min length terminations and can be fitted to panels between 1/16in - 3/16in (1.6 - 4.75mm) thick with approximately 1.5in (38mm) rear of panel projection.
The operating temperature range is -20 to +55 deg C, with storage conditions being -40 to +85 deg C.
• Marsh Bellofram Europe: contact details and other news