Monitoring motors and predicting failure
Electric motor problems occur for a variety of reasons, writes Michael Herring, but are most likely to arise from bearing failures with insulation deterioration a 'close second'.
Electric motor problems occur for a variety of reasons, ranging from basic design faults and poor manufacturing quality to problems caused by application and site conditions.
Specifically though, they are most likely to arise from bearing failures - probably the most common cause - with insulation deterioration following a close second.
While not trivialising the effect on plant operational efficiency that motor bearing failure will confer, established vibration analysis methods can readily pinpoint the potential for mechanical parts failure and trigger preventative measures.
However, up until now, the plant engineer has had a more complex task on hand, both in anticipating insulation failures and in determining the root cause of motor windings problems after they occur.
Early identification of a weak motor and its replacement or repair during an outage is demonstrably less expensive in comparison to plant downtime and rushed repairs.
Fortunately there are now specific condition monitoring techniques available that provide the ability to monitor motor performance, identify early indications of potential trouble and, better still, help to predict and proactively minimise problems by non-instrusive on-line methods.
One novel non-intrusive approach, developed by Glasgow Caledonian University, proposes the use of RF antennae to pick up radio interference generated during the motor's commutation process, then to store, process and analyse resultant data to reveal complex internal problems.
* Insulation deterioration - but before examining more conventional insulation resistance testing methods, a look at the causes of insulation deterioration, that can be detected by predictive maintenance testing, may go some way to help minimise their effects: * Thermal conditions - poor cooling is a common cause of insulation overtemperature caused by plugged cooling ducts or accumulated dust on windings.
Elevated temperatures can cause insulation to become brittle and/or shrink.
Shrinkage allows the winding to vibrate, eventually allowing the copper winding to contact the steel core of the motor with catastrophic results.
This shrinkage can also lead to winding wedges being loosened or lost, or the coil side packing allowing too much movement between coils.
Wear between coil and slot leads to breakdown of the remaining insulation and partial discharges increase, causing oxidation and erosion.
Winding temperature can be elevated to a damaging level by cyclic, heavy-load starting.
Heat is retained in the windings and in the core material, leading to cracked rotor bars.
* Contamination - moisture and electrical circuits are a combination to be avoided at all costs, but moisture is not the only contaminant that threatens performance.
While reaction to chemical contamination is an obvious cause of insulation deterioration, oil contamination is the most common culprit.
It can cause current leakage to increase and it can encourage accumulation of abrasive dust, brought in with the cooling air, that erodes insulation.
* Voltage conditions - most general purpose induction motors are more tolerant of small overvoltage than they are of undervoltage.
Undervoltage creates insulation temperature stress.
A motor operating at lower than specified voltage runs hotter.
Conversely, significant repeated overvoltage exposure, and particularly transient voltage spikes, can lead to 'turn-to-turn' and 'phase-to-phase' short circuits.
When turn insulation fails, a short circuit loop ensues causing the motor winding to act as an autotransformer - the shorted turn serves as the secondary and the remainder of the phase as a primary.
The motor is not prevented from running but the undetected, underlying condition causes progressive heat migration and damaging consequences.
* Simple insulation tests - there are a number of simple tests to determine if motor windings are approaching failure - DC Coil Resistance Test, Insulation Resistance Test, Polarisation Index Test, DC High Potential Test and Surge Comparison Test.
These procedures can reveal whether winding insulation is deteriorating or if there are localised flaws that will eventually escalate into total winding failure.
* DC coil resistance test - this technique compares the coil phases' resistance to each other in order to locate poor connections, open windings and shorted windings or turns.
However it is not capable of predicting turn-to-turn failures.
* Insulation resistance test - the most common tool for diagnosing insulation breakdown.
In this procedure the motor frame is grounded and a megohmmeter imposes a DC voltage, typically 500, 1000 or 2000V on the motor winding.
A sound winding will produce readout in hundreds or thousands of megohms.
A minimal acceptable reading will be 1 megohm plus 1 megohm/1000V of the motors rated voltage.
For example, the minimal acceptable resistance for a 460V motor is 1.46 megohms.
It is important to recognise that IR test readings are highly temperature and moisture sensitive.
Test motors should ideally be out of service long enough to assume ambient temperature and preclude condensation.
IR readings should be corrected in line with tables provided with test instrumentation.
* Polarisation index test - this takes IR testing one step further.
As the DC test voltage is maintained, insulation molecules polarise, resulting in a gradual increase in the resistance reading.
This ability decreases with ageing.
By measuring leakage currents from windings to ground at specific intervals, the plant engineer can establish a polarisation index.
By observing trendable test results over a given period the ageing and subsequent loss of insulation integrity can be determined.
* DC high potential test - weaknesses that might escape the scrutiny of IR and PI tests may well be identified by this procedure since it provides information on the dielectric strength of the insulation.
The recommended test voltage - double the motor rating plus 1000V - is gradually applied in step increments up to the maximum.
The resultant plot should be displayed as a straight line; any abrupt upswing in the plot slope would indicate an insulation flaw and the test procedure should be halted in this event to prevent winding failure.
* Surge comparison test - probably the newest of the classic tests to determine insulation condition, it detects turn-to-turn, coil-to-coil, and phase-to-phase defects that cannot be determined by any other method.
It is premised on the principle that in a motor with no winding defects, all three-phase windings are identical.
Each is tested against the other with brief DC voltage pulses.
Reflected pulse images of two identical windings appear as a single trace.
The waveform deviations from this pattern clearly indicate any turn-to-turn shorts or winding-to-ground flaws.
Electric motor test instrumentation specialists, Whitelegg Machines, offer a comprehensive range of single and multi-function testers.
Featuring digital output capability for interfacing with computer systems.
These instruments allow the plant engineer to manipulate motor test data and integrate findings with other pertinent conditioning monitoring and maintenance data.
*About the author - Michael Herring is sales director of Whitelegg Machines, based in the UK.
Not what you're looking for? Search the site.
Categories
- Machine Tools: Cutting (3,970)
- Machine Tools: Metalforming, shearing, folding and punching (1,512)
- Machine Tools: moulding (1,081)
- Cutting tools (1,805)
- Welding and Joining (1,509)
- Finishing, preparation, coating and painting (1,041)
- Automation and assembly systems (1,101)
- Manufacturing support (8,686)
- Industry news, commerce, exhibitions, education (8,254)
- Packaging (2,867)
- Specialist Manufacturing Sectors and Metals Producing (1,334)
- Books, CDs and Videos (198)
- IT for manufacturing management and production (3,167)
- IT for engineering, industrial and commercial applications (4,850)
- Manufacturing IT hardware and communications (1,570)
- Used machinery and machine tools (30)
- Materials handling and storage (942)
- Wood and non-metallics working (73)
- Metrology instruments and systems (3,832)
- Testing and quality control systems and services (4,987)
- Subcontracting services (1,165)